BS 7912:2012+A1:2017
Withdrawn
Power cables with XLPE insulation and metal sheath, and their accessories, for rated voltages from 66 kV (Um = 72.5 kV) to 132 kV (Um = 145 kV)
Hardcopy , PDF
English
07-20-2017
10-15-2023
| Committee |
GEL/20/16
|
| DocumentType |
Standard
|
| Pages |
0
|
| PublisherName |
British Standards Institution
|
| Status |
Withdrawn
|
| Supersedes |
This British Standard specifies tests and requirements for power cables with XLPE insulation and metal sheath and their accessories for rated voltages from 66kV (U m=72.5kV) to 132kV (U m=145kV) for fixed installations.
NOTE1 Cable systems to this standard do not normally have high electrical stresses at the conductor or insulation screen. If the calculated nominal electrical stresses at the conductor screen will be higher than 8.0kV/mm and/or at the insulation screen higher than 4.0 kV/mm, then attention is drawn to the need to conduct a prequalification test in accordance with IEC60840:2011 , Clause 13.
This British Standard is applicable to single-core cables and three-core cables with separate cores and to their accessories for usual conditions of installation and operation. It is not applicable to special cables and their accessories, such as those designed for submarine cables, for which modification to the standard tests might be necessary or special test conditions might need to be devised.
NOTE2 Annex A gives tests and requirements for cable bonding leads. Annex B gives tests and requirements for sheath voltage limiters (SVLs), while Annex C gives tests and requirements for link housings. Annex D gives an additional water blocking test for phase conductors.