EN 61238-1:2003
Superseded
View Superseded by
Compression and mechanical connectors for power cables for rated voltages up to 36 kV (Um = 42 kV) - Part 1: Test methods and requirements
08-19-2003
02-09-2022
EN IEC 61238-1-3:2019
EN IEC 61238-1-1:2019
EN IEC 61238-1-2:2019
INTRODUCTION
1 Scope and object
2 Normative references
3 Definitions
4 Symbols
5 General
5.1 Conductor
5.2 Connectors and tooling
5.3 Range of approval
6 Electrical tests
6.1 Installation
6.2 Measurements
6.3 Heat cycle test
6.4 Assessment of results
6.5 Requirements
7 Mechanical tests
7.1 Method
7.2 Requirements
8 Test report
Annex A (normative) Equalizers and their preparation
Annex B (normative) Measurements
Annex C (informative) Recommendations to improve accuracy
of measurement
Annex D (informative) Determination of the value of the
short-circuit-current
Annex E (normative) Calculation method
Annex F (informative) Explanation of the calculation method
Annex G (informative) Explanation of the temperature profile
Annex H (informative) Explanation of the statistical method
of assessing results of tests on
electrical connectors
Annex ZA (normative) Normative references to international
publications with their corresponding
European publications
Bibliography
Applies to compression and mechanical connectors for power cables for rated voltages up to 30 kV (Um = 36 kV), e.g. buried cables or cables installed in buildings, having - conductors complying with EN 60228 and EN 60228A with cross-sectional areas 10 mm2 and greater for copper and 16 mm2 and greater for aluminium, - a maximum continuous conductor temperature not exceeding 90 °C. This standard is not applicable to connectors for overhead conductors, which are designed for special mechanical requirements, or to separable connectors with a sliding contact or multi-core connectors (i.e. ring connectors). Although it is not possible to define precisely the service conditions for all applications, two broad classes of connectors have been identified. Class A These are connectors intended for electricity distribution or industrial networks in which they can be subjected to short-circuits of relatively high intensity and duration. As a consequence, Class A connectors are suitable for the majority of applications. Class B These are connectors for networks in which overloads or short-circuits are rapidly cleared by the installed protective devices, e.g. fast-acting fuses. Depending on the application, the connectors are subjected to the following tests: Class A: heat cycle and short-circuit tests. Class B: heat cycle tests only. The object of this standard is to define the type test methods and requirements, which apply to compression and mechanical connectors for power cables with copper or aluminium conductors. Formerly, approval for such products has been achieved on the basis of national standards and specifications and/or the demonstration of satisfactory service performance. The publication of this IEC standard does not invalidate existing approvals. However, products approved according to these earlier standards or specifications cannot claim approval to this IEC standard unless specifically tested to it. After they have been made, these tests need not be repeated un
| Committee |
CLC/TC 20
|
| DocumentType |
Standard
|
| PublisherName |
European Committee for Standards - Electrical
|
| Status |
Superseded
|
| SupersededBy |
| Standards | Relationship |
| NF EN 61238-1 : 2003 | Identical |
| IEC 61238-1:2003 | Identical |
| NBN EN 61238-1 : 2004 | Identical |
| NEN EN IEC 61238-1 : 2003 | Identical |
| I.S. EN 61238-1:2003 | Identical |
| PN EN 61238-1 : 2004 | Identical |
| VDE 0220-100 : 2004 | Identical |
| DIN EN 61238-1 : 2004 | Identical |
| BS EN 61238-1:2003 | Identical |
| CEI EN 61238-1 : 2004 | Identical |
| UNE-EN 61238-1:2006 | Identical |