IEC 60332-3-21:2000

Superseded

Superseded

View Superseded by

Tests on electric cables under fire conditions - Part 3-21: Test for vertical flame spread of vertically-mounted bunched wires or cables - Category A F/R

Available format(s)

Hardcopy , PDF

Language(s)

English - French

Published date

10-09-2000

Superseded date

09-12-2022

US$114.00
Excluding Tax where applicable
Summarise this standard

FOREWORD
INTRODUCTION
1 Scope
2 Normative references
3 Definitions
4 Test apparatus
      4.1 General
      4.2 Ignition source
5 Test procedure
      5.1 Test sample
      5.2 Determination of the number of test pieces
      5.3 Mounting of the test sample
      5.4 Flame application time
6 Evaluation of test results
7 Performance requirements
8 Retest procedure
9 Test report
Annex A (normative) Guidance on cable selection for type
                    approval testing
Annex B (informative) Recommended performance requirements
Figure 1 - Typical arrangement and spacing of cables mounted
           on both sides of the standard ladder (category
           A F/R)
Table A.1 - Summary of test conditions

IEC 60332-3-21:2000 Specifies method of test for the assessment of vertical flame spread of vertically-mounted bunched wires or cables, electrical or optical, under defined conditions. The test is intended for type approval testing. The requirements for the selection of cables for testing are given. The flame spread is measured as the extent of damage of the cable sample. This procedure may be used to demonstrate the cable's ability to limit flame spread. Covers category A F/R and relates only to power cables of conductor cross-sectional area greater than 35 mm2 installed on the test ladder in a spaced configuration on the front and rear to achieve a nominal total volume of non-metallic material of 7 l/m of test sample. The flame application time is 40 min. This method of mounting is intended for special cable designs used in particular installations when required in the cable specification. Category A F/R is not intended for general use. A recommended performance requirement is also given.It has the status of a horizontal standard in accordance with IEC Guide 104.

Committee
TC 20
DevelopmentNote
Supersedes IEC 60332-3 (03/2001) Stability Date: 2017. (09/2017)