BS EN 61482-1-1:2009

Superseded

Superseded

A superseded Standard is one, which is fully replaced by another Standard, which is a new edition of the same Standard.

View Superseded by

Live working. Protective clothing against the thermal hazards of an electric arc Test methods. Method 1. Determination of the arc rating (ATPV or EBT50) of flame resistant materials for clothing

Available format(s)

Hardcopy , PDF

Language(s)

English

Published date

31-07-2010

Superseded date

16-09-2019

Superseded by

BS EN IEC 61482-1-1:2019

£272.00
Excluding VAT
Summarise this standard

1 Scope
2 Normative references
3 Terms, definitions and symbols
4 Principle of the test methods
5 Significance and use of the test methods
6 Test apparatus
7 Precautions
8 Specimen preparation
9 Calibration
10 Test apparatus care and maintenance
11 Test procedures
12 Interpretation of results
13 Test report
Annex A (normative) - Measurement of char length
Annex B (informative) - Logistic regression technique
Annex C (informative) - Heat attenuation factor
Annex ZA (normative) - Normative references to international
         publications with their corresponding European
         publications
Bibliography

Defines test methods to measure the arc thermal performance value of materials intended for use in heat- and flame-resistant clothing for workers exposed to the thermal effects of electric arcs and the function of garments using these materials.

Committee
PEL/78
DevelopmentNote
Supersedes DD CLC/TS 61482-1 & 07/30173365 DC. (07/2010)
DocumentType
Standard
Pages
44
PublisherName
British Standards Institution
Status
Superseded
SupersededBy
Supersedes
UnderRevision

This part of IEC 61482 specifies test methods to measure the arc thermal performance value of materials intended for use in heat- and flame-resistant clothing for workers exposed to the thermal effects of electric arcs and the function of garments using these materials. These test methods measure the arc thermal performance value of materials which meet the following requirements: less than 100 mm char length and less than 2 s afterflame after removal from flame, when tested in accordance with ISO 15025, procedure B (bottom-edge ignition) on the outer material, and the char length measured using a modified ISO method as described in Annex A.

These methods are used to measure and describe the properties of materials, products, assemblies or garments, in response to convective and radiant energy generated by an electric arc in open air under controlled laboratory conditions.

The materials used in these methods are in the form of flat specimens for method A and garments for method B.

Method A is used to determine the arc rating of materials and material assemblies when tested in a flat configuration.

Method B is used to measure garment response, not arc rating, to an arc exposure including all the garment findings, sewing thread, fastenings, fabrics and other accessories when tested on a male mannequin torso. Method B is also used for accident replication.

It is the responsibility of the user of this part of IEC 61482 to establish appropriate safety and health practices prior to use. For specific precautions, see Clause 7.

The test methods in this part of IEC 61482 are not directed to classify by protection classes. Methods determining protection classes are prescribed in IEC 61482-1-2.

Standards Relationship
IEC 61482-1-1:2009 Identical
EN 61482-1-1:2009 Identical
I.S. EN 61482-1-1:2009 Equivalent

⚠

A newer version of this standard is available.